FIRE DETECTION & ALARM SYSTEMS / CONVENTIONAL

Fire detection systems are systems designed to discover fires early in their development when time will still be available for the safe evacuation of occupants. Bristol offers a complete range of fire detection and alarm systems complying to international standards.

SPECIFICATIONS

MODEL B61-801/02 B61-801/04 B61-801/08 B61-801/16
Standard EN 54-2 / EN 54-4
Zones 2 4 8 16
Power Supply 220V / 230 VAC / AC110V
Battery Size 7Ah / 12V
Frequency 50 / 60Hz
Input Current 0.35A
Loop Voltage 15VDC ~ 28VDC, 300mA
Fault Output Volt-free 1A/24VDC
Auxiliary Power Output 15VDC ~ 28VDC, Standby 20mA and Action 500mA
Temperature 0⁰C ~ 40⁰C
Humidity ≤ 95%, non-condensing
Dimension 430*330*105mm
Installation Wall-mounted
Cable 1.5mm2 or above shield cable

SPECIFICATIONS

MODEL B61-1001
Standard EN 54-7
Operating Voltage 9VDC ~ 28VDC
Quiescent Current ≤60uA
Alarm Current 10mA ≤I ≤ 50mA
LED indicator Red, flashing every 2s ~ 4s when standby; Illuminating when alarm fire
Remote indicator output 10kΩ resistor is required
Power-Up Time ≤ 10s
Wiring Method Polarized two-wire
Ingress Protection Rating IP32
Temperature -10⁰C ~+ 55⁰C
Humidity ≤95%, non-condensing
Dimension Diameter: 100mm, Height: 43mm (w/out base)
Weight About 120g

SPECIFICATIONS

MODEL Series BFE-C2WBI
Standard Dimension H600mm x W600mm x D300mm
Front Fascia Powder Coated / SS Brush / SS Mirror
Back Box Powder Coated / SS Brush / SS Mirror
Hinge Round Bar / SS Piano Hinges
Lock SS Round Latch Lock

SPECIFICATIONS

MODEL B61-2001
Standard EN 54-5
Operating Voltage 9VDC ~ 28VDC
Quiescent Current ≤60uA
Alarm Current 10mA ≤I ≤ 50mA
LED indicator Red, flashing every 2s ~ 4s when standby; Illuminating when alarm fire
Remote indicator output 10kΩ resistor is required
Power-Up Time ≤ 10s
Class A1R
Wiring Method Polarized two-wire
Ingress Protection Rating IP32
Temperature -10⁰C ~+ 55⁰C
Humidity ≤95%, non-condensing
Dimension Diameter: 100mm, Height: 43mm (w/out base)
Weight About 120g

SPECIFICATIONS

MODEL BF-SH-0115-2 BF-SH-0115-3 BF-SH-0115-4
Wiring Configuration 2-Wire 3-Wire with Remote Indicator Output 4-Wire with Relay Output
Standard EN 54-5 / EN 54-7
Voltage Range 12-30VDC
Standby Current 55µA
Alarm Current @ 24VDC 40mA 30mA 40mA
Thermal Setting 58ºC
Response Grade Comply to EN54, Grade 1
Ambient Temperature -10ºC to 55ºC
Material Fire-Proof Plastic
Dimensions 102mm(Dia)x58mm(H)
Weight 155g 157g 165g
Color White

SPECIFICATIONS

MODEL B61-5101
Standard EN 54-11
Operating Voltage 12VDC ~ 28VDC
Standby Current ≤0.5mA
Alarm Current ≤20mA (equivalent resistance is 470 / 1W)
LED indicator Red, Illuminating when alarm fire
Wiring Two-wire
Class Type A, indoor use
Ingress Protection Rating IP43
Temperature -10⁰C ~ + 55⁰C
Humidity ≤95%, non-condensing
Dimensions (LxWxH): 88mm x 88mm x 58mm (w/ back box)
(LxWxH): 88mm x 88mm x 23mm (w/out back box)
Weight About 160g (w/ back box)
About 107g (w/out back box)

SPECIFICATIONS

MODEL B61-6301
Standard EN 54-3
Operating Voltage 20VDC ~ 28VDC
Alarm Current ≤35mA
Flashing Frequency 1.4 x (1± 20%) Hz
Ingress Protection Rating IP21C
Temperature -10⁰C ~ + 50⁰C
Humidity ≤95%, non-condensing
Dimensions (LxWxH): 152mm x 91mm x 49.5mm
Weight About 210g

SPECIFICATIONS

MODEL Series BF-AB-0418
Standard BS EN 54-3
Voltage 24VDC
Current 25mA
Sound Output 93dB @ 1m
Movement Motor, Pinion and Striker
Movement Feature DC Motor, Acetral Gear Wheel, Steel Striker
Material Steel Plate
Base Plate Molded Black Polycarbonate
Dimensions Ø6″ (152mm) x 58mm (H)